Control mode:ON/OFF control or PID
Power:AC85-242V 50/60Hz
Display accuracy:1%FS
Input type:K;E;S;J;B;PT100;CU50
XMT-3000 Series temperature control instrument can replace the traditional pull yards -type or potentiometer type digital display meter, which uses the touch buttons can freely set, single-row LED display, with a fixed PID control or NO/OFF return difference control can elect, and return difference is adjustable, also have sensor error correction function. The instrument have a reliable control performance, cost-effective and wide application and so on.
I.Technical Indexs
1,Input type and measuring range:
K(0~1300C) E(0~800C) S(400~1600C) J(0~1000C)
B(800~1800C)PT100(-50.0~200.0C; -200~600C) Cu50(-50.0~150.0C)
Note: The instrument input type and measuring range subject to the meter label.
2,Display accuracy:±1%F·S±1B Additional cold junction compensation error≤2C
3,Control mode:ON/OFF control(return difference is adjustable)or PID control
4,Setting range of return difference: 1~20C,
5,Control proportion band(P):±9C or ±0.9C when temperature display has decimal point.
6,PID control period:30 seconds
7,Sensor error translation scope amendment:-20~20C
8,Output mode:Relay contact capacity AC220V/5A;
Drivng solid relay signal:driving electric current ≥ 15mA,voltage ≥ 9V
9,Power:AC85~242V 50Hz/60Hz
Power consumption: less than 3W or other according to customer requirement
10,Work environment:temperature 0~50.0C, relative humidity ≤ 85%RH, without corrode and strong electric radiation.
11,External dimension(mm): 48× 48× 90 Installation hole: 44× 44
II.Instrument panel(consult)
(1)Display window: Under the normal state, it displays the measured
temperature value.
(2)Output indicator (OUT): When the meter has output ,the light is bright;
when output is close, the indicator is out at the same time.
(3)Data increasing key():Under the normal display state, pressing the
key can increase the temperature set value;using in combination with
the key to enter the parameters modification state.
(4)Data decreasing key():Under the normal display state, pressing the
key can reduce the temperature set value;using in combination with the
key to enter the parameters modification state.
Model Sense:
XMT __ - 3 __ __ __ -Suffix
1 2 3 4
Blank 1:External size and Installation hole(mm):
'Empty':80×160×80 76×152;
'S':160×80×80 152×76; 'A':96×96×80 92×92; 'B':60×120×105 56×114;
'E':48×96×80 44×92; 'F':96×48×80 92×44; 'D':72×72×100 68×68; 'G':48×48×90 44×44;'K':24×48×90 23×45
Blank 2:Control output mode:
'0': two place control,relay output; '4': fixed PID control,relay output;
'5': Drivng solid relay signaloutput; 7': Drivng SCR zero passed pulse signal output
Blank 3:Alarm mode: '0':no alarm; '1':one upper limit alarm;
Blank 4:Input mode: '1': Thermocouple; '2': resistance
Suffix:'D': 30A high-power relay output