Customization: | Available |
---|---|
Customized: | Non-Customized |
Certification: | RoHS, CE, ISO |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Series | Attention | Name | Setting range | Remark | Ex- Factory |
|
|
0 | - | Appointed data | Determined by and | Pressorfor 3 second and set the temperature setting value you need | - |
First Menu |
1 |
AL |
High-limit alarm |
Determined by and | - | Random |
2 | SC | Measurement deviation |
-20.0~20.0 | Measuring value can be modified through increasing or decreasing this data. | 0 | |
3 |
P |
Proportion time | 0~99.9~200 | When the P↑,the proportion and differential function↑;If the P↓,the proportion and differential function↓ When P=0,the meter is ON/OFF control. |
15.0 | |
4 |
I |
Calculus time |
0~3000 | It's used to adjust static difference. To increse it ,the static difference will bereduced,but when it is too high,the static difference will drift instability. |
240 | |
5 |
d |
Differential time | 0~200 | It's used to adjust the overshoot in the First time,to increase it can reduce the overshoot. |
30 | |
6 | t | Control period | 2~ 120S | Control output period | 20 | |
7 |
Hy |
Main control by drop in level | 0.1~50.0 |
It only controls at ON/OFF |
1.0 |
|
8 |
At |
Parameter setting itself |
on/off |
off-shut itself function; on-open itself function Select 'on'only can adjust for one time,and then turn back to 'off' |
OFF |
|
9 |
Loc |
Electronics lock |
0~50 |
Loc=0 all the parameter can be revised Loc=1 only the appointed data can be revised |
0 |
|
Second Menu |
9 | Loc | Electronics lock |
0~50 | idem | 0 |
10 |
Sn |
Input specification |
- |
Input type Max. temperature range CU50 -50~150ºC/-90~270ºF,PT100 -199~600ºC/-199~1080ºF, K -30~1300ºC/-54~2340ºF, E -30~700ºC/-54~1260ºF, J -30~900ºC/-54~1620ºF, T -199~400ºC/-199~720ºF, S -30~1600ºC/-54~2880ºF |
K |
|
11 | dP | point | 0~1 | dP =0 display no point, dP =1 display point |
0 | |
12 | dIL | Set lower limit | dIL≤dIH | Temperature range refer to Sn | 0 | |
13 | dIH | Set upper limit | 400 | |||
14 | CF | ºC or ºF select |
- | C:ºC F:ºF |
C | |
15 |
PF |
Filt modulus |
0~50 |
It is the software filter constant of measurement sampling.The constant ↑,the measurement antijamming capability↑,but the measurement speed and system response time ↓ | 20 |