  • High Quality Temperature Controller Thermostat (XMTD-918)
  • High Quality Temperature Controller Thermostat (XMTD-918)
  • High Quality Temperature Controller Thermostat (XMTD-918)
Find Similar Products

Basic Info.

Model NO.
XMTD-918
Display Type
LED
Size
72*72
Transport Package
1PCS/Box
Specification
ISO 9001: 2008Others
Trademark
CJ
Origin
China
HS Code
9032900090
Production Capacity
100000PCS/Year

Product Description

Specifications

XMT-908 intelligence-ability temperature controller is a kind of high performance & reliability intelligence-ability temperature control meter, they are widely used in the automatic control system of the temperature, chemical, ceramics, light, metal, petrochemical and heat treatment industry
High Quality Temperature Controller Thermostat (XMTD-918)
Main technical specification
1. Measurement deviation: ≤ ± 0.5%F. S± 1
2. Cold end compensating deviation: ≤ ± 2.0C
3. Sampling cycle: 0.5S
4. Control cycle: Relay output 2120S, other is 2S.
5. Relay output contact capacity: AC250V/7A (resistance load) or AC250V/0.3A (perceptual
Load)
6. Driving controllable pulse output: ≥ 3V scope, ≥ 40us width's over zero or trigger contact pulse
7. Driving solid relay signal output: Driving electric current≥ 15mA, voltage≥ 9V.
8. Continuous PID: 010mA (load 500± 200Ω ), 420mA (load 250± 100Ω ), or 05V (load≥ 100kΩ ), 15V (load≥ 100kΩ )
9. Exterior and hole size: 72× 72× 110    68× 68
10. Power: AC85V242V, 50/60Hz
11. Working condition: Temperature 0-50.0C, relative humidity≤ 85%RH, without corrode and strong electric radiation.

Meaning of the model code

XMT _ -  9   _   8   __
      (1) (2) (3) (4) (5)
(1)The surface dimension(mm):
Blank:160×80×120 Installation hole 152×76; 
A:96×96×110 Installation hole 92×92;
D:72×72×110 Installation hole 68×68; 
E: 48×96×110 Installation hole 44×92; 
F:96×48×110 Installation hole 92×44; 
S:80×160×120 Installation hole 76×156
G:48×48×110 Installation hole 44×44 

(2)Control Mode: '9':4-key gentle push-switch setting,double row 4-LED digital display,PID and ON/OFF(P=0)control can select. 
(3)Additional alarm:'0':no alarm ; '1':one group alarm; '3':two group alarms '5':voice alarm
(4)Signal input type:'8':freely exchange signal 

(5)Suffix:
Main control output method:
'Blank':relay's open and closed contact output;
'A':Single-phase over-zero spark pulse; 
'A3':Three-phase over-zero spark pulse;
'B':Single-phase shift-phase spark pulse; 
'B3':Three-phase shift-phase spark pulse;
'C':0~10mA or 4~20mA constant electric current output 
'G':ON/OFF solid state relay(SSR)adjustment output;
Auxiliary ways:
'K':with RS485 or RS232 communication module interface; 
'Wt':with micro-printer output signal;



Connection Method

High Quality Temperature Controller Thermostat (XMTD-918)


Code setting mode
Series Code Name Setting range Manual  Ex-Factory
0 SP Setting value of temperature Determined by P-SL P-SH Control output corresponds to indicator light "OUT".
Please refer to "5.2,The SP setting"
50
1 AL1 Alarm 1 Determined by P-SL,P-SH when the upper and lower limit alarm, it is0~50.0 when the positive deviation alarm and negative deviation alarm  
Please refer to ALP1
Corresponds to indicator light"ALM1"
300
2 AL2
()
Alarm 2 Please refer to ALP2
Corresponds to "ALM2" indicator light
100
3 P Proportion modulus 0~200 When the P↑,the proportion and differential
function↓;If the P↓,the proportion and
differential function↑
When P=0,the meter is under ON/OFF control
15
4 I Calculus time 0~2000S   240
5 d Differential time 0~200S   30
6 At Setting itself ON/OFF ON:open function of setting inself
OFF:close function of setting itself
OFF
7 t Control period 2~120S This function is no meaning under "ON/OFF". It is preseted 20s in factory. 20
8 Hy Main control by
drop in level
0.1~50.0 Only have meaning when main control output is ON/OFF(P=0) 1.0
9 Hy1 drop in level of
AL1
0.1~50.0 It is used as setting of drop in level
for AL1 relay output  
1.0
10 Hy2
()
drop in level of
AL2
 
0.1~50.0 It is used as setting of drop in level
for AL2 relay output 
1.0
11 Pb Sensor error amendment ±20.0 The sensor have deviation can use item to revisal 0
12 FILT Filt modulus 0~50 Is the software filter constants of  measurement sampling.The constant ↑,the measurements antijamming capability measurements antijamming capability↑, but the measurement and system time ↓ 20
13 dp Display precision 0~1 1: have radix point,0: have not radix point 0
14 P-SH The max.value of temperature range - They are used to reset proper temperature range as per user'application.
As for the Max. temperature range for
different inputs, please refer to Sn,
P-SH≥P-SL
400
15 P-SL The min.value of temperature range - 0
16 OUTL
()
The min. value
Of allowable output  
0~OUTH Can achieve low and high output limiter. Meaningless when manual and ON/OFF control 0
17 OUTH
()
The max. value
Of allowable output
OUTL~200 200
18 ALP1 AL1  and its output definition 0~4 'o':indicate no alarm
'1':upper limit alarm
'2':lower limit alarm
'3': positive deviation alarm
'4': negative deviation alarm
1
19 ALP2() AL2 and its output definition 0~4 0
20 COOL System function choice 0~1 '0':reverse control(heat)
'1':positive control(cool)
0
21 OPPO() Open power output 0~100 Soft start function that meters coefficient after first output of electric power 0
22 LOCK Code lock 0~50 LOCK=0,all the parameter can be revised
LOCK=1,only the SP can be revised
LOCK>1,all the parameter can not be revised
0
23 Sn Input type CU50()
PT100()
PT100()
K(),E(),J()
T(),S()
Input type      Max. temperature range
CU50          -50.0~150.0ºC
PT1            -200.0~200.0ºC
PT2            -200.0~600.0ºC
K              -30.0~1300ºC
E              -30.0~700.0ºC
J               -30.0~900.0ºC
T             -200.0~400.0ºC
S              -30.0~1600ºC
 
24 OP-A
()
Output type  
RLP()
SSR()
Zero()
Mut()
0~10MA()
4~20MA()
RLP Relay output
SSR Solid state relay
Zero Zero passed trigger of controlled silicon
Mut Controlled silicon phase-shifted trigger
0~10MA linearity current control output
4~20MA linearity current control output
 
 
RLP


Certificate
High Quality Temperature Controller Thermostat (XMTD-918)


 Packaging Detailed
High Quality Temperature Controller Thermostat (XMTD-918)

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier