Customization: | Available |
---|---|
Customized: | Customized |
Certification: | RoHS, CE |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Series | Code | Name | Setting range | Manual | Ex-Factory |
0 | SP | Setting value of temperature | Determined by P-SL P-SH | Control output corresponds to indicator light "OUT". Please refer to "5.2,The SP setting" |
50 |
1 | AL1 | Alarm 1 | Determined by P-SL,P-SH when the upper and lower limit alarm, it is0~50.0 when the positive deviation alarm and negative deviation alarm | Please refer to ALP1 Corresponds to indicator light"ALM1" |
300 |
2 | AL2 () |
Alarm 2 | Please refer to ALP2 Corresponds to "ALM2" indicator light |
100 | |
3 | P | Proportion modulus | 0~200 | When the P↑,the proportion and differential function↓;If the P↓,the proportion and differential function↑ When P=0,the meter is under ON/OFF control |
15 |
4 | I | Calculus time | 0~2000S | 240 | |
5 | d | Differential time | 0~200S | 30 | |
6 | At | Setting itself | ON/OFF | ON:open function of setting inself OFF:close function of setting itself |
OFF |
7 | t | Control period | 2~120S | This function is no meaning under "ON/OFF". It is preseted 20s in factory. | 20 |
8 | Hy | Main control by drop in level |
0.1~50.0 | Only have meaning when main control output is ON/OFF(P=0) | 1.0 |
9 | Hy1 | drop in level of AL1 |
0.1~50.0 | It is used as setting of drop in level for AL1 relay output |
1.0 |
10 | Hy2 () |
drop in level of AL2 |
0.1~50.0 | It is used as setting of drop in level for AL2 relay output |
1.0 |
11 | Pb | Sensor error amendment | ±20.0 | The sensor have deviation can use item to revisal | 0 |
12 | FILT | Filt modulus | 0~50 | Is the software filter constants of measurement sampling.The constant ↑,the measurements antijamming capability measurements antijamming capability↑, but the measurement and system time ↓ | 20 |
13 | dp | Display precision | 0~1 | 1: have radix point,0: have not radix point | 0 |
14 | P-SH | The max.value of temperature range | - | They are used to reset proper temperature range as per user'application. As for the Max. temperature range for different inputs, please refer to Sn, P-SH≥P-SL |
400 |
15 | P-SL | The min.value of temperature range | - | 0 | |
16 | OUTL () |
The min. value Of allowable output |
0~OUTH | Can achieve low and high output limiter. Meaningless when manual and ON/OFF control | 0 |
17 | OUTH () |
The max. value Of allowable output |
OUTL~200 | 200 | |
18 | ALP1 | AL1 and its output definition | 0~4 | 'o':indicate no alarm '1':upper limit alarm '2':lower limit alarm '3': positive deviation alarm '4': negative deviation alarm |
1 |
19 | ALP2() | AL2 and its output definition | 0~4 | 0 | |
20 | COOL | System function choice | 0~1 | '0':reverse control(heat) '1':positive control(cool) |
0 |
21 | OPPO() | Open power output | 0~100 | Soft start function that meters coefficient after first output of electric power | 0 |
22 | LOCK | Code lock | 0~50 | LOCK=0,all the parameter can be revised LOCK=1,only the SP can be revised LOCK>1,all the parameter can not be revised |
0 |
23 | Sn | Input type | CU50() PT100() PT100() K(),E(),J() T(),S() |
Input type Max. temperature range CU50 -50.0~150.0ºC PT1 -200.0~200.0ºC PT2 -200.0~600.0ºC K -30.0~1300ºC E -30.0~700.0ºC J -30.0~900.0ºC T -200.0~400.0ºC S -30.0~1600ºC |
|
24 | OP-A () |
Output type | RLP() SSR() Zero() Mut() 0~10MA() 4~20MA() |
RLP Relay output SSR Solid state relay Zero Zero passed trigger of controlled silicon Mut Controlled silicon phase-shifted trigger 0~10MA linearity current control output 4~20MA linearity current control output |
RLP |