Cj Relay Output Digital LED Pid Temperature Controller (XMTA-618)

Product Details
Customization: Available
Customized: Customized
Certification: RoHS, CE, ISO
Manufacturer/Factory & Trading Company
Gold Member Since 2006

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
86
Year of Establishment
2000-08-23
  • Cj Relay Output Digital LED Pid Temperature Controller (XMTA-618)
  • Cj Relay Output Digital LED Pid Temperature Controller (XMTA-618)
  • Cj Relay Output Digital LED Pid Temperature Controller (XMTA-618)
  • Cj Relay Output Digital LED Pid Temperature Controller (XMTA-618)
Find Similar Products

Basic Info.

Model NO.
XMTA-618
Display Type
LED
Size
96*96
Control Type
Digital
Type
Temperature Controller
Control Method
Electronic Type
Usage
Temperature Control
Transport Package
1PCS/Box
Specification
ISO 9001: 2008 Others
Trademark
CJ
Origin
China
HS Code
9032900090
Production Capacity
100000PCS/Year

Product Description

Specifications

Temperature controller
On/off
PID control
Temperature meter are dual row 3-LED display
Input: CU50; PT100; J; E; K; T

Cj Relay Output Digital LED Pid Temperature Controller (XMTA-618)

XMT*608 series intelligent temperature controller, is double row 3-LED display and include on/off, PID control, including with parameter of self-setting function. This temperature meter respectively display temperature measurement value (PV) and temperature set value (SV) under normal mode; When it is time temperature control, respectively display temperature measurement value (PV) and running time count down (SV), and also provide kinds of time control method selection; The controller can input kinds of signal which are used interchangeably, it adopt ON/OFFP=0PID control, allowing an easy parameter setting and convenient inputting, is widely used over temperature automatic control systems of machinerychemicalceramicslight industrialmetallurgypetrifaction and heat treatment and so on.

Main technical Indexes

1, Measurement deviation: ± 0.5%F· S± 1B, Cold end compensating deviation≤ ± 2C
2, Input(can be selected): CU50(-50~150), PT100(-199~600), K(-30~999),
E(-30~700), J(-30~900), T(199~400)
3, Relay output contact capacity: AC220V 5A(resistance load)
Period 2~120s can be adjusted.
4, Drivng solid relay signal output: Driving electric current >15m A voltage >9V,
Period is 2S
5, Power: AC85V~242V, 50/60Hz
6, Work environment: Temperature 0~50.0C, relative humidity≤ 85%RH, without corrode and strong electric radiation.

Model sense
                 XMT(    )-6   (    )     8     (   )
                           1          2     3     4        5
1:External size and Installation hole(mm)
Empty   160×80×90    152×76         A   96×96×90   92×92
D   72×72×90     68×68         E    48×96×90   44×92
F   96×48×90    92×44          G    48×48×100   44×44
S   80×160×90   76×152      B    60×120×90   56×116
C   80×120×35   wall set installation
2. Operation display method:'6': 3-key gentel push-switch setting, double row digital display, have PID adjustment
3. An additional alarm:
Blank or '0': indicates no alarm;'1': High limit touch alarm;'2': low limit touch alarm
4. Input signal classification: '8' : Input signal can interchange free
5. Suffix:  None: relay output           G: solid state relay output

 


Series
Code Name Setting range Remark Ex-Factory





First









Menu
 

0

-
Appointed data Determined
by
and
Press∧or∨for 3 second and set the temperature setting value  you need
-

1
AL
 
High/Low-limit
alarm
Determined
by
and

-

Random
2 SC Measurement
deviation
-20.0~20.0 Measuring value can be modified through increasing or decreasing this data. 0

3
P
 

Proportion time
0~99.9~200 When the P↑,the proportion and differential
function↓;If the P↓,the proportion and
differential function↑
When P=0,the meter is ON/OFF control.
15.0

4
I
 

Calculus time
0~999 It's used to adjust static difference. To increse it,the static difference will be reduced, but if it is too high, the static difference will drift instability. 240
5 d Differential time 0~200
 
30

6

t

Control period

2~120S
When it leaves factory, SSR is 2s;
Relay is 20s.
When P=0, it makes no sense.

20

7

Hy
Main control by drop in level
0.1~50.0

It only controls at ON/OFF

1.0

8
At
 

Parameter setting itself

/
OFF_shut itself function  ;
ON_open itself function
Select ' ON'only can adjust for one time,and then turn back to 'OFF '

OFF

9
Loc
 
Electronics
lock

0~50
Loc=0 all the parameter can be revised
Loc=1 only the appointed data can be revised

0

 



Second







Menu
 
10 Loc Electronics
lock
0~50 idem 0
11 Sn Input type - CU50\PT100\K\E\J(\T; K

12

dIL

Set lower limit


dIL≤dIH
CU50(-50~150)\
PT100(-80~600)\
K(-30~999)\E(-30~700)\
J(-30~900)\T(199~400)
 

0

13

dIH

Set upper limit

400


14

PF
 


Filt modulus


0~50
It is the software filter constant of  measurement sampling.The constant ↑,the measurement antijamming capability↑,but the measurement speed  and system response time ↓

20
15 COL System function
choice

ON/OFF
ON:positive control(cooling control)
OFF:reverse control(heating control)

OFF

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier