Meaning of the model code
XMT _ - 9 _ 8 __
(1) ( 2) (3) (4) (5)
(1)The surface dimension(mm):
Blank:160×80×120 Installation hole 152×76;
A:96×96×110 Installation hole 92×92;
D:72×72×110 Installation hole 68×68;
E: 48×96×110 Installation hole 44×92;
F:96×48×110 Installation hole 92×44;
S:80×160×120 Installation hole 76×156
G:48×48×110 Installation hole 44×44
(2)Control Mode: '9':4-key gentle push-switch setting,double row 4-LED digital display,PID and ON/OFF(P=0)control can select.
(3)Additional alarm:'0':no alarm ; '1':one group alarm; '3':two group alarms '5':voice alarm
(4)Signal input type:'8':freely exchange signal
(5)Suffix:
Main control output method:
'Blank':relay's open and closed contact output;
'A':Single-phase over-zero spark pulse;
'A3':Three-phase over-zero spark pulse;
'B':Single-phase shift-phase spark pulse;
'B3':Three-phase shift-phase spark pulse;
'C':0~10mA or 4~20mA constant electric current output
'G':ON/OFF solid state relay(SSR)adjustment output;
Auxiliary ways:
'K':with RS485 or RS232 communication module interface;
'Wt':with micro-printer output signal;
Inner parameter
Series |
Code | Name | Setting range | Manual | Ex-Factory |
0 | SP | Setting value of temperature | Determined by P-SL P-SH | Output corresponds to "OUT" indicator light | 50.0 |
1 | AL1 | Alarm 1 | Determined by P-SL,P-SH when the upper and lower limit alarm, it is0~50.0 when the positive deviation alarm and negative deviation alarm | please refer to ALP1 Corresponds to "ALM1" indicator light |
300 |
2 | AL2 | Alarm 2 | please refer to ALP2 Corresponds to "ALM2" indicator light |
100 | |
3 | P | Proportion modulus | 0~100 | When the P↑, the proportion and differential function↓; If the P↓, the proportion and differential function↑ When P=0, the meter is ON/OFF control |
15 |
4 | I | Calculus time | 0~2000S | 240 | |
5 | d | Differential time | 0~200S | 30 | |
6 | At | Setting itself | ON/OFF | ON: open setting itself function OFF: close setting itself function |
OFF |
7 | t | Control period | 1~120S | The movements cycle ON/OFF of Setting relays control is no meaning, Relay is 20S, other is 2S. |
20 |
8 | Hy | Main control by drop in level |
0.1~50.0 | Only have meaning when main control output is ON/OFF(P=0) | 1.0 |
9 | Hy-1 | drop in level of AL1 |
0.1~50.0 | It is used as setting of drop in level for AL1 relay output |
1.0 |
10 | Hy-2 | drop in level of AL2 |
0.1~50.0 | It is used as setting of drop in level for AL2 relay output |
1.0 |
11 | Pb | Sensor error amendment | ±20.0 | The sensor have deviation can use item to revisal | 0 |
12 | FILT | Filt modulus | 0~50 | Is the software filter constants of measurement sampling. The constant ↑, the measurements antijamming capability↑, but the measurement and system time ↓. | 20 |
13 | dp | Display precision | 0~1 | 1: have radix point; 0: have not radix point | 0 |
14 | P-SH | The max.value of temperature range | - | They are used to reset proper temperature range as per user'application. As for the Max. temperature range for different inputs, please refer to Sn, P-SH≥P-SL |
1300 |
15 | P-SL | The min.value of temperature range | - | 0 | |
16 | OUTL | The min. value of allowable output |
0~OUTH | Can achieve low and high output limiter. Meaningless when manual and ON/OFF control | 0 |
17 | OUTH | The max. value of allowable output |
OUTL~200 | 200 | |
18 | ALP1 | Alarm1 and output definition | 0~4 | 'o':indicate no alarm; '1':upper limit alarm '2':lower limit alarm; '3': Upper-limit (deviation) Alarm; '4': Lower-limit (deviation) Alarm; |
- |
19 | ALP2 | Alarm2 and output definition | 0~4 | - | |
20 | COOL | System function choice | 0~1 | '0': reverse control(heat) '1': positive control(cool) |
0 |
21 | OPPO | Open power output | 0~100 | Soft start functionthat meters coefficient after first export of electric power | 0 |
22 | LOCK | Code lock | 0~50 | LOCK=0, all the parameter can be revised LOCK=1, only the SP can be revised LOCK>1, all the parameter can not be revised |
0 |
23 | Sn | Input type | CU50( ) PT100( ) PT100( ) K( )\E( )\J( ) T( )\S( ) |
CU50 (-50.0~150.0ºC) ; PT1 (-200.0~200.0ºC) ; PT2 (-200.0~600.0ºC) ;K (0~1300ºC) ; E (0~700.0ºC) ; J (0~900.0ºC) ; T (-200~400.0ºC) ; S (0~1600ºC) ; |
|
24 | OP-A | Output type | RLP( ) SSR( ) Zero( ) Mut( ) 0~10MA( ) 4~20MA( ) |
RLP Relay output mode SSR Solid state relay Zero SCR zero voltage switching Mut SCR phase-shift trigger 0~10MA linearity control electric current output 4~20MA linearity control electric current output |
__ |