Series | Code | Name | Setting range | Manual | Ex-Factory |
0 | SP | Appointed data | Determined by P-SL P-SH | Output corresponds to "OUT" indicator light | 50.0 |
1 | AL-1 | Alarm 1 | Determined by P-SL,P-SH when the upper and lower limit alarm, it is0~50.0 when the positive deviation alarm and negative deviation alarm | please refer to ALP1 Corresponds to "ALM1" indicator light |
300 |
2 | AL-2 | Alarm 2 | please refer to ALP2 Corresponds to "ALM2" indicator light |
100 | |
3 | P | Proportion modulus | 0~100 | When the P↑,the proportion and differential function↓;If the P↓,the proportion and differential function↑ When P=0,the meter is ON/OFF control |
15 |
4 | I | Calculus time | 0~2000S | 240 | |
5 | d | Differential time | 0~200S | 30 | |
6 | At | Setting itself | ON/OFF | ON:open setting inself function OFF:close setting itself function |
OFF |
7 | t | Control period | 1~120S | The movements period ON/OFF of Setting relays control is no meaning, Relay is 20S,other is 2S. |
20 |
8 | Hy | Main control by drop in level |
0.1~50.0 | Only have meaning when main control output is ON/OFF(P=0) | 1.0 |
9 | Hy-1 | Alarm 1 drop in level |
0.1~50.0 | It has use drop in level setting of alarm 1 contact output | 1.0 |
10 | Hy-2 | Alarm 2 drop in level |
0.1~50.0 | It has use drop in level setting of alarm 2 contact output | 1.0 |
11 | Pb | Sensor error amendment | ±20.0 | The sensor have deviation can use item to revisal | 0 |
12 | FILT | Filt modulus | 0~50 | Is the software filter constants of measurement sampling.The constant ↑,the measurements antijamming capability measurements antijamming capability↑, but the measurement and system time ↓ | 20 |
13 | dp | Show accuracy | 0~1 | 0: have radix point,1: have no radix point | 0 |
14 | P-SH | Display the high limit | - | Limit the parameters of "SP" setting range. Range please refer to Sn, P-SH≥P-SL |
1300 |
15 | P-SL | Display the low limit | - | 0 | |
16 | OUTL | Allow exports min value | 0~OUTH | Can achieve low and high output limiter. Meaningless when manual and ON/OFF | 0 |
17 | OUTH | Allow exports max value | OUTL~200 | 200 | |
18 | ALP1 | Alarm1 and output definition | 0~4 | 'o':indicate no alarm '1':upper limit alarm '2':lower limit alarm '3': positive deviation alarm '4': negative deviation alarm |
- |
19 | ALP2 | Alarm2 and output definition | 0~4 | - | |
20 | COOL | System function choice | 0~1 | '0':reverse control(heat) '1':positive control(cool) |
0 |
21 | OPPO | Open power output | 0~100 | Soft start functionthat meters coefficient after first export of electric power | 0 |
22 | LOCK | Code lock | 0~50 | LOCK=0,all the parameter can be revised LOCK=1,only the "sp" can be revised LOCK>1,all the parameter can not be revised |
0 |
23 | Sn | Input type | CU50( ) PT100( ) PT100( ) K( ),E( ),J( ) T( ),S( ) |
CU50 (-50.0~150.0ºC) ; PT1 (-200.0~200.0ºC) ; PT2 (-200.0~600.0ºC) ;K (0~1300ºC) ; E (0~700.0ºC) ; J (0~900.0ºC) ; T (-200~400.0ºC) ; S (0~1600ºC) ; |
|
24 | OP-A | Output type | RLP( ) SSR( ) Zero( ) Mut( ) 0~10MA( ) 4~20MA( ) |
RLP Relayoutput mode SSR Solid state relay Zero controllable silicon contact signal when it exceed zero output mode Mut controllable silicon phase trigger contact output mode 0~10MA linearity control electric current output 4~20MA linearity control electric current output |