Zhejiang, China
Business Type:
Manufacturer/Factory & Trading Company
Number of Employees:
113
Year of Establishment:
2000-08-23
Management System Certification:
ISO9001:2008
Average Lead Time:
Peak season lead time: one month
Off season lead time: one month
OEM/ODM Service
Sample Available
Distributorship Cooperation

Temperature Controller, Temperature Meter, Temperature Regulator manufacturer / supplier in China, offering Intelligence Dual Row 3-LED Display Temperature Controller (XMTA-618), Xmtdw-1001/2 Digital Temperature Controller for Industrial, Series of Wr Electric Thermocouples and Wz Thermal Resiatance and so on.

Gold Member Since 2006
Audited Supplier
Supplier Homepage Products 1 Temperature Controllers Intelligence Dual Row 3-LED Display Temperature Controller (XMTA-618)

Intelligence Dual Row 3-LED Display Temperature Controller (XMTA-618)

Get Latest Price
Min. Order / Reference FOB Price
1 Piece US $18.8/ Piece
Port: Ningbo, China
Production Capacity: 100000PCS/Year
Payment Terms: L/C, T/T, Western Union, Paypal
Customized: Customized
Certification: RoHS, UL, CE, ISO
Display Type: LED
Size: 96*96
Control Type: Digital
Type: Temperature Controller

You Might Also Like

Loading...

Basic Info

Model NO.: XMTA-618
Control Method: Electronic Type
Usage: Temperature Control
Trademark: CJ
Transport Package: 1PCS/Box
Specification: ISO 9001: 2008 Others
Origin: China
HS Code: 9032900090

Product Description

Specifications

Temperature controller
On/off
PID control
Temperature meter are dual row 3-LED display
Input: CU50; PT100; J; E; K; T



XMT*608 series intelligent temperature controller, is double row 3-LED display and include on/off, PID control, including with parameter of self-setting function. This temperature meter respectively display temperature measurement value (PV) and temperature set value (SV) under normal mode; When it is time temperature control, respectively display temperature measurement value (PV) and running time count down (SV), and also provide kinds of time control method selection; The controller can input kinds of signal which are used interchangeably, it adopt ON/OFFP=0PID control, allowing an easy parameter setting and convenient inputting, is widely used over temperature automatic control systems of machinerychemicalceramicslight industrialmetallurgypetrifaction and heat treatment and so on.

Main technical Indexes

1, Measurement deviation: ± 0.5%F· S± 1B, Cold end compensating deviation≤ ± 2C
2, Input(can be selected): CU50(-50~150), PT100(-199~600), K(-30~999),
E(-30~700), J(-30~900), T(199~400)
3, Relay output contact capacity: AC220V 5A(resistance load)
Period 2~120s can be adjusted.
4, Drivng solid relay signal output: Driving electric current >15m A voltage >9V,
Period is 2S
5, Power: AC85V~242V, 50/60Hz
6, Work environment: Temperature 0~50.0C, relative humidity≤ 85%RH, without corrode and strong electric radiation.

Model sense
                 XMT(    )-6   (    )     8     (   )
                           1          2     3     4        5
1:External size and Installation hole(mm)
Empty   160×80×90    152×76         A   96×96×90   92×92
D   72×72×90     68×68         E    48×96×90   44×92
F   96×48×90    92×44          G    48×48×100   44×44
S   80×160×90   76×152      B    60×120×90   56×116
C   80×120×35   wall set installation
2. Operation display method:'6': 3-key gentel push-switch setting, double row digital display, have PID adjustment
3. An additional alarm:
Blank or '0': indicates no alarm;'1': High limit touch alarm;'2': low limit touch alarm
4. Input signal classification: '8' : Input signal can interchange free
5. Suffix:  None: relay output           G: solid state relay output

 


Series
CodeNameSetting rangeRemarkEx-Factory





First









Menu
 

0

-
Appointed dataDetermined
by
and
Press∧or∨for 3 second and set the temperature setting value  you need
-

1
AL
 
High/Low-limit
alarm
Determined
by
and

-

Random
2SCMeasurement
deviation
-20.0~20.0Measuring value can be modified through increasing or decreasing this data.0

3
P
 

Proportion time
0~99.9~200When the P↑,the proportion and differential
function↓;If the P↓,the proportion and
differential function↑
When P=0,the meter is ON/OFF control.
15.0

4
I
 

Calculus time
0~999It's used to adjust static difference. To increse it,the static difference will be reduced, but if it is too high, the static difference will drift instability.240
5dDifferential time0~200
 
30

6

t

Control period

2~120S
When it leaves factory, SSR is 2s;
Relay is 20s.
When P=0, it makes no sense.

20

7

Hy
Main control by drop in level
0.1~50.0

It only controls at ON/OFF

1.0

8
At
 

Parameter setting itself

/
OFF_shut itself function  ;
ON_open itself function
Select ' ON'only can adjust for one time,and then turn back to 'OFF '

OFF

9
Loc
 
Electronics
lock

0~50
Loc=0 all the parameter can be revised
Loc=1 only the appointed data can be revised

0

 



Second







Menu
 
10LocElectronics
lock
0~50idem0
11SnInput type-CU50\PT100\K\E\J(\T;K

12

dIL

Set lower limit


dIL≤dIH
CU50(-50~150)\
PT100(-80~600)\
K(-30~999)\E(-30~700)\
J(-30~900)\T(199~400)
 

0

13

dIH

Set upper limit

400


14

PF
 


Filt modulus


0~50
It is the software filter constant of  measurement sampling.The constant ↑,the measurement antijamming capability↑,but the measurement speed  and system response time ↓

20
15COLSystem function
choice

ON/OFF
ON:positive control(cooling control)
OFF:reverse control(heating control)

OFF