Series | Code | Name | Setting range | Manual | Remarks |
0 | SP | Appointed data | Determined by P-SL P-SH | - | 50.0 |
1 |
tE | Timing seting |
1~59.59 |
please refer to Corresponds to "TE" indicator light |
10 |
2 |
AL1 | Temperature alarm |
fixed value alarm : Determined by P-SL,P-SH; follow-up alarm: 0.0~100.0 . |
please refer to Corresponds to "AL1" indicator light |
100 |
3 |
P | Proportion modulus |
0.0~200.0 |
When the P↑,the proportion and differential function↑; If the P↓,the proportion and differential function↓ When P=0,the meter is ON/OFF control. |
15.0 |
4 |
I | Calculus time | 0~3000S |
It's used to adjust static difference. To increse it ,the static difference will be reduced,but if it is too high, the static difference will drift instability. | 240 |
5 | d | Differential time | 0~200S | 30 | |
6 | At | Setting itself function |
OFF:close the function ON:open the function |
Selection of the Setting itself function |
OFF |
7 | t | Control period | 2~120 S | the movements period ON/OFF of Setting relays control is no meaning |
20 |
8 | Hy | Main control by drop in level |
0.1~100.0 | Only have meaning when main control output is ON/OFF(P=0) |
1.0 |
9 | Hy1 | Alarm 1 drop in level |
0.1~100.0 | It has use drop in level setting of alarm contact output |
1.0 |
10 | Pb | Sensor error amendment |
±20.0 | The sensor have deviation can use item to revisal |
0 |
11 |
FILE |
Filt modulus |
0~50 |
It is the software filter constant of measurement sampling.The constant ↑,the measurement antijamming capability↑,but the measurement speed and system response time ↓ | 20 |
12 | Lock | Code lock | 0~50 | =all the parameter can be revised,or it can't. | 0 |
13 |
Sn |
Input type |
CU50(),PT100(),K(),E(),J(),T(),S(), |
CU50(-50~150.0), PT100(-199.9~600.0), K(-30~1300),E(-30~700), J(-30~900),T(199~400), S(-30~1600) |
|
14 | P_SL | Display the high limit |
P-SL~full range | Can set the high limit displaying input signal |
250 |
15 | P_SL | Display the low limit |
Range start ~P-SH | Can set the low limit displaying input signal |
0 |
16 |
outH | Allow output max value |
OUTL~100.0 |
Can output high amplitude limiting, manual and ON/OFF output with no effect |
100.0 |
17 |
outL | Allow output min value |
0.0~OUTH |
Can output low limit condition, manual and ON/OFF control output with no effect |
0.0 |
18 | ALP | Alarm output definition |
0~1 |
'0' upper limit alarm '1' follow-up alarm |
0 |
19 | tEP | Time unit choice | 0~1 | 0:minute and second display 1:hour and minute display |
0 |
20 | COOL | System function choice |
ON/ OFF | OFF:reverse control(heating control) ON:positive control(cooling control) |
OFF |
21 |
oP_R | Output method |
- |
SSR solid state relay RLP relay output method |
RLP |
22 |
oppO | Open power output power |
0~100 |
Soft start function that meters coefficient after first output of electric power |
0 |
23 |
CF | Fahrenheit and degree centigrade selecting |
C/F |
C:ºC ; F:ºF |
C |
24 | dP | Display accuracy | ON/ OFF | 0: have radix point, 1: have no radix point |
OFF |
25 |
Int |
Time function selection |
0~3(Time control side be switched on) |
0:common temperature control 1:start timing when it reaches the temperature,and the built-in buzzer will give an alarm output after reaching the time, the controller keep on heating; 2:start timing when it reaches the temperature,and the built-in buzzer will |
0 |
give an alarm output after reaching the time, the controller stop heating; 3:regular temperature control(no alarm)+time relay function: start timing when the power is on, alarm relay attracting after reaching the time . |