Series | Code | Name | Setting range | Manual | Remarks | |||||
First Menu |
0 | LOCK | Code lock | 0~50 | 18-all the parameter can be revised, |
18 | ||||
1 | Sn | Input type | -- | CU50,Pt100,K,E,J | K | |||||
2 |
ALP |
Alarm define |
0~6 |
0:no alarm,1:upper limit alarm,2:low limit alarm,3:upper windage alarm, 4 :lower windage alarm 5:between besides alarm,6:between inside alarm |
1 |
|||||
3 | t | Output cycle | 0~120 S | relay control action cycle setting | 10 S | |||||
4 | dp | display accuracy | 0~1 | 0. no decimal; 1.have decimal | 0 | |||||
5 | P-SH | Upper limit | P-SL~full range | this parameter resreict enactment value's upper |
according request | |||||
6 | P-SL | lower limit | Range jumping-off ~P-SH | this parameter resreict enactment value's low |
according request | |||||
7 | OPB | Assistant output method | 0~2 | no Assistant output; 1.RS485 communication 2.Mini pinter |
0 | |||||
8 | Add | address | 1~64 (1~9999) |
Meter's NO (in minitype as print times) |
1 | |||||
9 | bt | baud rate | 0~3 | 0:1200; 1:2400; 3:4800; 4:9600 |
9600 | |||||
Second Menu |
10 | SP+N(1~2) | N channels control setting | Range by P-SL,P-SH decide | Control value setting | default |
||||
11 | AL+N | Alarm value setting | Range by P-SL,P-SH decide | Output mode decide by 'AL-P' | default | |||||
12 | SC+N | Sensor error amendment | ±20.0 | The sensor have deviation can use item to revisal |
0.0 | |||||
13 | P+N | Proportion modulus | 0~100 | When P↑, proportion function↓, clash↓, but too big will add the heating time When P=0, the instrument is ON/OFF control. |
15.0 | |||||
14 |
I+N |
Calculus time |
0~3000 |
Set integral time so as to unchain residual deflection caused by proportion control. To increase it, the static difference will be reduced, but when it is too high ,thestatic difference will drift instability. |
240 |
|||||
15 |
d+N |
differential time | 0~200S |
Set differential time to avoid fluctuation of output so as to improve the steady of control. |
30 |
|||||
16 | Hy+N | Main control by drop in level | 0.1~50.0 | It only controls at ON/OFF | 1.0 | |||||
17 | At+N | Setting itself | 0~1 | 0:close setting itself function 1:open setting itself function |
0 |