Product Description
Summary
CJLCA-908 Series LCD Intelligent Instruments are developed with the following characteristics:
LCD display
Microcontroller (SCM)
RTD, thermocouple, voltage, current and other free input signals.
Ten kinds of alarm modes.
Manual and automatic switching.
Standard MODBUS RTU communication protocol.
In addition to the conventional two-position master mode, artificial intelligent regulator PID control algorithm based on he traditional PID control algorithm and fuzzy control theory
In a variety of different systems, the instrument can be satisfied by a majority of self-tuning control effect parameters, with no overshoot, disturbance rejection, and other characteristics.
Technical Specifications
Measurement Accuracy: ±0.5%ºC
Cold Junction Compensation Error:≤±2.0ºC
Sampling Period:0.5 second
Control Period: relay output is from 2seconds to120 seconds, whiles others is 2seconds
Output Relay Rating:5A/ AC 220V (resistance load) or 0.3A / AC 220V (inductive load)
Drive Solid State Relay Output: driving current≥15mA, voltage ≥ 9V
Input AC Power Supply: AC85V ~ 242V (switch power supply), 50/60Hz, or other special orders
Working Environment:Temperature 0~50.0ºC, Humidity≤85%RH, non-condensing
Product code:
CJLC(1)-9(2)8(3)
(1) Meter faceplate and Installation dimension(mm):
Blank: 160×80×130 156×76;
A: 96×96×110 92×92;
D: 72×72×110 68×68;
(2)Alarm:
"0": no set alarm
"1": one alarm
"5": voice alarm
"3": two group alarm (upper limit, lower limit, positive deviation alarm and negative deviation alarm discretionary setting)
(3)Control method: Blank: Relay contact output
"B": Single-phase shift-phase trigger adjustment
"C": 0-10mA or 4-20mA constant electric current output
"G":solid relay output
"K"communication function