Customization: | Available |
---|---|
Customized: | Customized |
Certification: | RoHS, CE, ISO |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Series | Code | Name | Setting range | Manual | Remarks | ||||
First Menu |
0 | LOCK | Code lock | 0~50 | LOCK=18,all the parameter can be revised | 18 | |||
1 | Sn | Input type | 0~4 | CU50,Pt100,K,E,J | K | ||||
2* |
ALP |
Alarm define |
0~6 |
0:no alarm,1:upper limit alarm,2:low limit alarm,3:upper warp alarm,4:low warp alarm, 5:between besides alarm, 6:between inside alarm |
1 |
||||
3 | t | Output cycle | 0~120 S | relay control action cycle setting | 10 S | ||||
4 | dp | display accuracy | 0~1 | 1: have radix point, 0: have not radix point |
0 | ||||
5 | P-SH | Upper limit | P-SL~full range | this parameter resreict enactment value's upper |
according request | ||||
6 |
P-SL |
lower limit |
Range jumping-off ~P-SH | this parameter resreict enactment value's low |
according request | ||||
7 |
OPB |
Assistant output method | 0~2 |
0:no Assistant output; 1:RS485 communication 2:Mini pinter |
0 |
||||
8 | Add | address | 1~64 (1~9999) |
Meter's NO (in minitype as print times) |
1 | ||||
9 | bt | baud rate | -- | 0:1200; 1:2400; 3:4800; 4:9600 |
9600 9600 |
||||
Second Menu |
10 |
SP+N(1~4) | N channels control setting | Range by P-SL,P-SH decide | Control value setting |
default |
|||
11 |
AL+N |
Alarm value setting | Range by P-SL,P-SH decide | Output mode decide by 'AL-P' |
default |
||||
12 | SC+N | Sensor error amendment | ±20.0 | The sensor have deviation can use item to revisal |
0 | ||||
13 |
P+N |
Proportion modulus |
0~100 |
When the P increase, the proportion function decrease. When P=0,the meter is ON/OFF control |
8 |
||||
14 |
I+N |
Integral time |
0~3000 |
Set integral time so as to unchain residual. Deflection caused by proportion control. To increase it, the static difference will be reduced, but when it is too high ,the static difference will drift instability. | 240 |
||||
15 |
d+N |
differential time |
0~200S |
Set the differential time,so as to avoid. The output's fluctuation,Improve the control's stability. | 30 |
||||
16 |
Hy+N |
Main control by drop in level |
0.1~50.0 |
- |
1.0 |
||||
17* | At+N | Setting itself | 0~1 | 0:close setting itself function 1:open setting inself function | 0 |