Series |
Code | Name | Setting range | Remark | Ex-Factory | |
First Menu |
0 |
- |
Appointed data | Determined by and |
Press∧or∨for 3 second and set the temperature setting value you need | - |
1 |
AL |
High/Low-limit alarm |
Determined by and |
- |
Random |
|
2 | SC | Measurement deviation |
-20.0~20.0 | Measuring value can be modified through increasing or decreasing this data. | 0 | |
3 |
P |
Proportion time |
0~99.9~200 | When the P↑,the proportion and differential function↓;If the P↓,the proportion and differential function↑ When P=0,the meter is ON/OFF control. |
15.0 | |
4 |
I |
Calculus time |
0~999 | It's used to adjust static difference. To increse it,the static difference will be reduced, but if it is too high, the static difference will drift instability. | 240 | |
5 | d | Differential time | 0~200 | 30 | ||
6 |
t |
Control period |
2~120S |
When it leaves factory, SSR is 2s; Relay is 20s. When P=0, it makes no sense. |
20 |
|
7 |
Hy |
Main control by drop in level | 0.1~50.0 |
It only controls at ON/OFF |
1.0 |
|
8 |
At |
Parameter setting itself |
/ |
OFF_shut itself function ; ON_open itself function Select ' ON'only can adjust for one time,and then turn back to 'OFF ' |
OFF |
|
9 |
Loc |
Electronics lock |
0~50 |
Loc=0 all the parameter can be revised Loc=1 only the appointed data can be revised |
0 |
|
Second Menu |
10 | Loc | Electronics lock |
0~50 | idem | 0 |
11 | Sn | Input type | - | CU50\PT100\K\E\J(\T; | K | |
12 |
dIL |
Set lower limit |
dIL≤dIH |
CU50(-50~150)\ PT100(-80~600)\ K(-30~999)\E(-30~700)\ J(-30~900)\T(199~400) |
0 |
|
13 |
dIH |
Set upper limit |
400 |
|||
14 |
PF |
Filt modulus |
0~50 |
It is the software filter constant of measurement sampling.The constant ↑,the measurement antijamming capability↑,but the measurement speed and system response time ↓ | 20 |
|
15 | COL | System function choice |
ON/OFF |
ON:positive control(cooling control) OFF:reverse control(heating control) |
OFF |