Temperature and Humidity Controller with 5 to 95%Rh (XMT-9007-8)

  • Audited Supplier
  • 21 yrs

Contact Supplier

Product Highlights

  • Dual Parameter Control: Simultaneously measures and controls temperature and humidity with real-time display.
  • Advanced PID Control: Offers PID and On/Off modes for precise temperature and humidity regulation.
  • RS485 Communication: Enables long-distance computer control via RS485 serial module.
  • Data Printing Function: Connects to mini printer to regularly print temperature and humidity records.
  • Long Data Retention: Power-off data retention time exceeds 10 years for reliable history storage.
  • Customizable Dimensions: Available in multiple sizes including 160x80, 96x96, 72x72, and 48x96 mm.
  • Versatile Sensor Options: Supports PT100 for temperature and PT100 or high molecular sensor for humidity.

Product Images of Temperature and Humidity Controller with 5 to 95%Rh (XMT-9007-8)

Temperature and Humidity Controller with 5 to 95%Rh (XMT-9007-8)
Temperature and Humidity Controller with 5 to 95%Rh (XMT-9007-8) pictures & photos
Temperature and Humidity Controller with 5 to 95%Rh (XMT-9007-8)
Temperature and Humidity Controller with 5 to 95%Rh (XMT-9007-8) pictures & photos
Temperature and Humidity Controller with 5 to 95%Rh (XMT-9007-8)
  • Temperature and Humidity Controller with 5 to 95%Rh (XMT-9007-8)
  • Temperature and Humidity Controller with 5 to 95%Rh (XMT-9007-8)
    Temperature and Humidity Controller with 5 to 95%Rh (XMT-9007-8)
  • Temperature and Humidity Controller with 5 to 95%Rh (XMT-9007-8)
    Temperature and Humidity Controller with 5 to 95%Rh (XMT-9007-8)

Find Similar Products

Product Description

The XMT9007-8 temperature & humidity instrument is an intelligence instrument based on the computer technique. It adopts a 2-row digital 8 high-light 7 sect LED and synchronous display both the humidity and drying temperature measured. The control parameters can be set by panel and displayed in real-time.



The user can choose below functions
1. Sensor: PT100 sensor for temperature measurement, PT100 OR high molecular sensor for the humidity measurement.
2. Control mode: PID and on/off mode for heat and humidity control. On/off mode for cool control. On/off control is convenient for using; PID control can improve the meter control precision.
3. Serial communication: The computer can make a long-distance control to the meter by RS485 serial module.
4. Print function: The meter can regularly print annals and sample value of temperature and humidity by connecting mini printer.



Main Technical Specifications
1. Accuracy: Temperature measurement accuracy +0.5%F. S+1.0character Humidity measurement accuracy + 0.2%F. S+1.0 character
2. Temperature measurement range: -50.0-150.0C
3. Output relay: AC220V 10A
4. Power-off data-retention time: Over 10 years
5. Work Power: AC220V± 10% 50Hz Power consumption less than 5W
6. Normal working ambience: Temperature: 0-50C, Relative humidity: 35%-85% without corrosive gas-free space
7. Power on, in case"-----"or "----", or "100% humidity" is always displayed in both the upper and lower row windows respectively, please, check if the wire of the sensor is broken, or if a case of short circuit or other problem, such as wrong connection, etc.
8. External dimension and Installation hole(mm): 160× 80× 125 Installation hole 152× 76



Sense of Model Code
         X M T(-)  -9007-8 (-)
                   1                2
1: the exterior size (mm):
 None: 160*80*120       hole: 152*76      
   "A":  96*96*110        hole: 92*92

   "D":  72*72*110        hole: 68*68             
   "F":  48*96*110        hole:44*92

2: suffix
  None: relay on-off output   
 "WT": with mini printer output function

   "K" : with RS485 PC communication function
  "C2": with electric current transfer output function




The panel specification(consult) 

Temperature and Humidity Controller with 5 to 95%Rh (XMT-9007-8)
Connection scheme (consult)

Temperature and Humidity Controller with 5 to 95%Rh (XMT-9007-8)Temperature and Humidity Controller with 5 to 95%Rh (XMT-9007-8)
Series Code Name Setting range Description Ex-factory
 
1
 
LOCK
 
Password
 
0~200
Lock=0, can modify adjust all parameters except Sn parameter. 
Lock=155, Sn parameter only can be set.
 
0
2 C1 Heating 
set value
-50.0~150.0 Set the heating temperature value
Please refer to "7.1\heating control"
50.0
 
3
 
RH
Humidifying 
set value
 
0.0~100
Set the humidifyingset value
Please refer to "7.2\humidifying control"
70.0
4 C2 Cooling 
set value
-50.0~150.0 Set cooling temperature value
Please refer to "7.3\cooling output"
60.0
5 OPB Expansion function 0~2 0: no;   1: communication function;
2: print function
0
6 BT Communication baud
 
1200\2400\4800\9600 9600
 
7
 
ADT
Communication address or print interval time 0~100
0~9999
Communication setting range:0~100
Print setting range:0~9999(minute)
 
1
 
8
 
tb
 
Cooling return difference
 
-20.0~20.0
When the parameter is set to a negative number, that cooling have delayed function, delay time is three minutes.
Please refer to "7.3\Cooling output"
 
0.5
 
9
 
P1
 
Proportionality factor
 
0~100.0
Proportional band determines the size of the heating system proportional gain, P1 is greater, the proportion role is smaller, overshoot is smaller, but too small will increase the heating time.
Set P1 = 0, heating turn to ON/OFF control status.
 
15.0
 
10
 
I1
 
Integration time
 
0~2000
Set integration time to remove the residual error of the proportional control, and too great slow system achieving balance time, too small will produce fluctuations.   
240
11 D1 Differential time 0~250 Set the differential time, in order to prevent fluctuation of the output and improve the stability of the control. 30
12 T1 Heating control cycle 2~120 The instrument is PID control, it is meaningful, it means the sum of closing time and opening time in the heating control output. 10
13 HY1 Heating return difference 0~50.0 When the heating implement ON/OFF control, it is useful.
Please refer to"7.1\Heating control".
1.0
 
14
 
AT1
Heating 
setting itself
 
0 or 1
AT1 = 0, turn off the heating setting itself function;
AT1 = 1, open the heating setting itself function. 
Please refer to instruction "VI\Setting itself " 
 
0
 
 
15
 
 
P2
 
 
Proportionality factor
 
 
0~100.0
Proportional band determines the size of the humidifying system proportional gain, P1 is greater, the proportion role is smaller, overshoot is smaller, but too small will increase the humidifying time.
Set P1 = 0, humidifying turn to ON/OFF control status.
 
 
15.0
 
16
 
I2
 
Integration time
 
0~2000
Set integration time to remove the residual error of the proportional control, and too great slow system achieving balance time, too small will produce fluctuations.  
240
 
17
 
D2
Differential time  
0~250
Set the differential time, in order to prevent fluctuation of the output and improve the stability of the control.  
30
 
18
 
T2
 
Humidifying control cycle
 
2~120
The instrument is PID control, it is meaningful, it means the sum of closing time and opening time in the humidifying control output. 10
 
19
 
HY2
Humidifying return difference 0.0~20.0 When the humidifying implement ON/OFF control, it is useful.
Please refer to"7.2\Humidifying control".
1.0
 
20
 
AT2
 
Humidifying setting itself
 
0 or 1
AT2 = 0, turn off the humidifying setting itself function;
AT2 = 1, open the humidifying setting itself function. 
Please refer to instruction "VI\Setting itself " 
 
0 
21 Sn Input type 0 or 1 0:Equipped with PT100 + PT100 sensors;
1:Equipped with PT100 + high molecular sensors;
1
 
22
 
SC1
Temperature sensor error  revise  
-20.0~20.0
When between the measured temperature and actual temperature have error, you can amend by this parameter.  
0.0
 
23
 
SC2
Humidity  sensor error  revise  
-20.0~20.0
When between the measured humidity and actual humidity have error, you can amend by this parameter.  
0.0
The second menu:(Print parameters)
Series Code Name Setting range Description Ex-factory
24 YER Year 0~99 Set the year of printing time.  __
25 YUE Month 1~12 Set the month of printing time. __
26 DA Day 1~31 Set the day of printing time.  __
27 HO Hour 0~23 Set the hour of printing time.  __
28 FEN Minute 0~59 Set the minute of printing time.  __

About the Supplier

This supplier has been audited by SGS. Verify the report on the official SGS website with ID "QIP-ASR223865". Items marked "verified" are certified.

Yuyao Gongyi Meter Co., Ltd.
Yuyao Gongyi Meter Co., Ltd.
Yuyao Gongyi Meter Co., Ltd.
Yuyao Gongyi Meter Co., Ltd.
Yuyao Gongyi Meter Co., Ltd.
Yuyao Gongyi Meter Co., Ltd.
Yuyao Gongyi Meter Co., Ltd.
Yuyao Gongyi Meter Co., Ltd.

About Our Factory & Business Background

verified Business Type
Manufacturer/Factory & Trading Company
Address
No. 9, Changqing Road, Yuyao, Ningbo, Zhejiang, China
verified Plant Area
4052 square meters
verified Number of Employees
86
verified Registered Capital
1,500,000 RMB
verified Terms of Payment
LC, T/T, PayPal, Western Union
verified International Commercial Terms(Incoterms)
FOB, CIF, CFR
verified Average Lead Time
Peak Season Lead Time: one month
Off Season Lead Time: one month
verified Nearest Port
Shanghai Port, Ningbo Port

Our Production Capability & Technical Expertise

verified Main Products
Temperature Controller, Temperature Sensor, Thermometer, Temperature Indicator, Temperature and Humidity Controller
verified Production Machines
Injection Molding Machine, SMT Production Line
verified ODM Service Available
Yes
verified OEM Service Available
Yes
verified R&D Engineers
2 people
verified Own Brand
Yes

Our Industry Experience & Global Business Record

verified Year of Establishment
2000-08-23
Export Year
2019-05-18
verified Main Markets
North America, South America, Africa
verified Number of Foreign Trading Staff
4
verified Overseas Agent/Branch
No

Our Certifications, Standards & Industry Recognition

verified Product Certification
CE

FAQ

What control modes are available?
The device supports both PID control for high precision and On/Off control for simple applications.
Can the device be controlled remotely?
Yes, it features RS485 serial communication allowing long-distance control by a computer.
Does the device support data printing?
Yes, it can connect to a mini printer to regularly print temperature and humidity records.
What are the available sensor options?
It supports PT100 for temperature and either PT100 or high molecular sensors for humidity.
How long does the device retain data after power loss?
The power-off data retention time is over 10 years.
Is the device size customizable?
Yes, it is available in various sizes such as 160x80, 96x96, 72x72, and 48x96 mm.

Send your message to this supplier

Contact Information
Recipient
Message

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now