Xmt-9007-8 Cj Temperature and Humidity Controller with 5 to 95%Rh

Product Details
Customization: Available
Customized: Customized
Certification: RoHS, ISO9001, CE, ISO
Manufacturer/Factory & Trading Company
Gold Member Since 2006

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
86
Year of Establishment
2000-08-23
  • Xmt-9007-8 Cj Temperature and Humidity Controller with 5 to 95%Rh
  • Xmt-9007-8 Cj Temperature and Humidity Controller with 5 to 95%Rh
  • Xmt-9007-8 Cj Temperature and Humidity Controller with 5 to 95%Rh
  • Xmt-9007-8 Cj Temperature and Humidity Controller with 5 to 95%Rh
  • Xmt-9007-8 Cj Temperature and Humidity Controller with 5 to 95%Rh
  • Xmt-9007-8 Cj Temperature and Humidity Controller with 5 to 95%Rh
Find Similar Products

Basic Info.

Model NO.
XMT-9007-8
Display Type
LED
Size
160*80
Control Type
Digital
Type
Temperature and Humidity Controller
Usage
Temperature and Humidity Control
Transport Package
1PCS/Box
Specification
ISO 9001: 2008Others
Trademark
CJ
Origin
China
HS Code
9032900090
Production Capacity
100000PCS/Year

Product Description

The XMT9007-8 temperature & humidity instrument is an intelligence instrument based on the computer technique. It adopts a 2-row digital 8 high-light 7 sect LED and synchronous display both the humidity and drying temperature measured. The control parameters can be set by panel and displayed in real-time.

The user can choose below functions
1. Sensor: PT100 sensor for temperature measurement, PT100 OR high molecular sensor for the humidity measurement.
2. Control mode: PID and on/off mode for heat and humidity control. On/off mode for cool control. On/off control is convenient for using; PID control can improve the meter control precision.
3. Serial communication: The computer can make a long-distance control to the meter by RS485 serial module.
4. Print function: The meter can regularly print annals and sample value of temperature and humidity by connecting mini printer.

Main Technical Specifications
1. Accuracy: Temperature measurement accuracy +0.5%F. S+1.0character Humidity measurement accuracy + 0.2%F. S+1.0 character
2. Temperature measurement range: -50.0-150.0C
3. Output relay: AC220V 10A
4. Power-off data-retention time: Over 10 years
5. Work Power: AC220V± 10% 50Hz Power consumption less than 5W
6. Normal working ambience: Temperature: 0-50C, Relative humidity: 35%-85% without corrosive gas-free space
7. Power on, in case"-----"or "----", or "100% humidity" is always displayed in both the upper and lower row windows respectively, please, check if the wire of the sensor is broken, or if a case of short circuit or other problem, such as wrong connection, etc.
8. External dimension and Installation hole(mm): 160× 80× 125 Installation hole 152× 76

Inner parameters:
Series Code Name Setting range Description Ex-factory
 
1
 
LOCK
 
Password
 
0~200
Lock=0, can modify adjust all parameters except Sn parameter. 
Lock=155, Sn parameter only can be set.
 
0
2 C1 Heating 
set value
-50.0~150.0 Set the heating temperature value
Please refer to "7.1\heating control"
50.0
 
3
 
RH
Humidifying 
set value
 
0.0~100
Set the humidifyingset value
Please refer to "7.2\humidifying control"
70.0
4 C2 Cooling 
set value
-50.0~150.0 Set cooling temperature value
Please refer to "7.3\cooling output"
60.0
5 OPB Expansion function 0~2 0: no;   1: communication function;
2: print function
0
6 BT Communication baud
 
1200\2400\4800\9600 9600
 
7
 
ADT
Communication address or print interval time 0~100
0~9999
Communication setting range:0~100
Print setting range:0~9999(minute)
 
1
 
8
 
tb
 
Cooling return difference
 
-20.0~20.0
When the parameter is set to a negative number, that cooling have delayed function, delay time is three minutes.
Please refer to "7.3\Cooling output"
 
0.5
 
9
 
P1
 
Proportionality factor
 
0~100.0
Proportional band determines the size of the heating system proportional gain, P1 is greater, the proportion role is smaller, overshoot is smaller, but too small will increase the heating time.
Set P1 = 0, heating turn to ON/OFF control status.
 
15.0
 
10
 
I1
 
Integration time
 
0~2000
Set integration time to remove the residual error of the proportional control, and too great slow system achieving balance time, too small will produce fluctuations.   
240
11 D1 Differential time 0~250 Set the differential time, in order to prevent fluctuation of the output and improve the stability of the control. 30
12 T1 Heating control cycle 2~120 The instrument is PID control, it is meaningful, it means the sum of closing time and opening time in the heating control output. 10
13 HY1 Heating return difference 0~50.0 When the heating implement ON/OFF control, it is useful.
Please refer to"7.1\Heating control".
1.0
 
14
 
AT1
Heating 
setting itself
 
0 or 1
AT1 = 0, turn off the heating setting itself function;
AT1 = 1, open the heating setting itself function. 
Please refer to instruction "VI\Setting itself " 
 
0
 
 
15
 
 
P2
 
 
Proportionality factor
 
 
0~100.0
Proportional band determines the size of the humidifying system proportional gain, P1 is greater, the proportion role is smaller, overshoot is smaller, but too small will increase the humidifying time.
Set P1 = 0, humidifying turn to ON/OFF control status.
 
 
15.0
 
16
 
I2
 
Integration time
 
0~2000
Set integration time to remove the residual error of the proportional control, and too great slow system achieving balance time, too small will produce fluctuations.  
240
 
17
 
D2
Differential time  
0~250
Set the differential time, in order to prevent fluctuation of the output and improve the stability of the control.  
30
 
18
 
T2
 
Humidifying control cycle
 
2~120
The instrument is PID control, it is meaningful, it means the sum of closing time and opening time in the humidifying control output. 10
 
19
 
HY2
Humidifying return difference 0.0~20.0 When the humidifying implement ON/OFF control, it is useful.
Please refer to"7.2\Humidifying control".
1.0
 
20
 
AT2
 
Humidifying setting itself
 
0 or 1
AT2 = 0, turn off the humidifying setting itself function;
AT2 = 1, open the humidifying setting itself function. 
Please refer to instruction "VI\Setting itself " 
 
21 Sn Input type 0 or 1 0:Equipped with PT100 + PT100 sensors;
1:Equipped with PT100 + high molecular sensors;
1
 
22
 
SC1
Temperature sensor error  revise  
-20.0~20.0
When between the measured temperature and actual temperature have error, you can amend by this parameter.  
0.0
 
23
 
SC2
Humidity  sensor error  revise  
-20.0~20.0
When between the measured humidity and actual humidity have error, you can amend by this parameter.  
0.0
The second menu:(Print parameters)
Series Code Name Setting range Description Ex-factory
24 YER Year 0~99 Set the year of printing time.  __
25 YUE Month 1~12 Set the month of printing time. __
26 DA Day 1~31 Set the day of printing time.  __
27 HO Hour 0~23 Set the hour of printing time.  __
28 FEN Minute 0~59 Set the minute of printing time.  __

Model definition:
      XMT (1)   9007-8(2)   
                       
(1)The exterior size and hole size(mm):
   None: 160×80×120,  152×76;   A: 96×96×110,  92×92;   D: 72×72×110,   68×68;      
E: 48×96×110,   44×92;   F: 96×48×110,   92×44;   S: 80×160×120,   76×152

9007-8:serial number, double row LED temperature and humidity show

(2)suffix: K:Communication function;        WT:Print function
 A:SCR zero-crossing trigger output    G:Solid state relay trigger output

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now